Moghal Brothers


Moghal Brothers

Knowledgebase
Moghal Brothers > Moghal Brothers Inquiry/Support > Knowledgebase

Ask a question:


MBCT-CR-300

Solution

 

 

 

 

MOGHAL BROTHERS COOLING TOWERS

MBCT-CR-300

Stainless Steel

 

GENERAL

1

Tower Model

MBCT-CR-300-SS

2

Type

Mechanical Induced Draft, Cross-Flow, Rectangular

 

 

 

 

DESIGN & OPERATING CONDITIONS

3

Circulating Water Flow rate, LPM

3900

4

Hot (Inlet) Water Temp, °C

37

5

Cold (Outlet) Water Temp, °C

32

6

Wet Bulb Temp, °C

27

7

Shipping Weight, kg (Approx)

1894

8

Operating Weight, kg (Approx)

5682

 

 

 

 

STRUCTURAL DETAILS

9

Number of Cells

01

10

Fans per Cell

01

11

Overall Dimension (L x W x H), mm

2950 x 3350 x 4360

12

Hot Water Inlet, (Nos. x DN) mm

02 x 100

13

Cold Water Outlet, (Nos x DN) mm

01 x 200

 

 

 

 

MATERIALS OF CONSTRUCTION

14

Frame Work

G.I (Dry Parts), SS304 Non Magnetic (Water Touching Parts)

15

Casing Walls

FRP

16

Packing (In-Fills)

Imported PVC with Integrated Drift Eliminators (High Temperature)

4 layers of 26" Packet

17

Fills Support

SS304

18

Fan Stack

FRP

19

Louvers

PVC

20

Water Distribution Trays

FRP

21

Cold Water Basin

FRP

22

Ladder

G.I

23

Bolts Nuts Washers (Wet Parts)

SS304 Non Magnetic

24

Bolts Nuts Washers (Dry Parts)

SS304 Non Magnetic

25

Access Door

FRP

26

Fan Guard

SS304

27

Belt Cover

FRP with Hinges.

 

 

 

 

MECHANICAL & ELECTRICAL EQUIPMENT

 

Fan 

28

Type

Axial Flow, Adjustable Pitch, Wide-Chord

29

Material of Construction

Casted Aluminum

30

Number of Blades per Fan

04

31

Total Diameter, mm

2000

32

Air Flow, m³/min

2000

33

Drive

Belt Driven

34

Electric Motor

 

35

Number

04

36

Type

TEFC, Insulation-F, IP 55

37

Origin / Make

Siemens

38

Rated, hp

7.5

 

 


 


 

 

 

MOGHAL BROTHERS COOLING TOWERS

MBCT-CR-300

G.I

 

GENERAL

1

Tower Model

MBCT-CR-300-GI

2

Type

Mechanical Induced Draft, Cross-Flow, Rectangular

 

 

 

 

DESIGN & OPERATING CONDITIONS

3

Circulating Water Flow rate, LPM

3900

4

Hot (Inlet) Water Temp, °C

37

5

Cold (Outlet) Water Temp, °C

32

6

Wet Bulb Temp, °C

27

7

Shipping Weight, kg (Approx)

1894

8

Operating Weight, kg (Approx)

5682

 

 

 

 

STRUCTURAL DETAILS

9

Number of Cells

01

10

Fans per Cell

01

11

Overall Dimension (L x W x H), mm

2950 x 3350 x 4360

12

Hot Water Inlet, (Nos. x DN) mm

02 x 100

13

Cold Water Outlet, (Nos x DN) mm

01 x 200

 

 

 

 

MATERIALS OF CONSTRUCTION

14

Frame Work

G.I

15

Casing Walls

FRP

16

Packing (In-Fills)

Imported PVC with Integrated Drift Eliminators (High Temperature)

4 layers of 26" Packet

17

Fills Support

G.I

18

Fan Stack

FRP

19

Louvers

PVC

20

Water Distribution Trays

FRP

21

Cold Water Basin

FRP

22

Ladder

G.I

23

Bolts Nuts Washers

SS304 Non Magnetic

24

Access Door

FRP

25

Fan Guard

G.I

26

Belt Cover

FRP

 

 

 

 

MECHANICAL & ELECTRICAL EQUIPMENT

 

Fan 

27

Type

Axial Flow, Adjustable Pitch, Wide-Chord

28

Material of Construction

Casted Aluminum

29

Number of Blades per Fan

04

30

Total Diameter, mm

2000

31

Air Flow, m³/min

1990

32

Drive

Belt Driven

33

Electric Motor

 

34

Number

04

35

Type

TEFC, Insulation-F, IP 55

36

Origin / Make

Siemens

37

Rated, hp

7.5

 

 


 

 
Was this article helpful? yes / no
Article details
Article ID: 14
Category: Cooling Towers
Date added: 2017-02-01 23:47:14
Views: 320
Rating (Votes): Article rated 3.2/5.0 (18)

 
« Go back